Emergency & Exit Lighting: The OBC and CEC Requirements That Get Buildings Rejected

Exit corridor leading to a stair door: a green running-man exit sign over the door, a directional exit sign hung from the ceiling, emergency battery units mounted high on the wall lighting the floor, and the stair in section.

"The exit signs are installed." Great. But are they on a transfer switch? Do the battery units provide 30 minutes or 120 minutes? Is the illumination at floor level actually 10 lux? These are the questions building inspectors ask - and the ones that delay occupancy permits when the answers are wrong.

Two Codes, One System

Emergency lighting in Ontario is designed to two separate codes that must be satisfied simultaneously; testing falls under the Ontario Fire Code:

Code Governs Key Sections
Ontario Building Code (OBC)Where emergency lighting is required, illumination levels, exit sign placementOBC 3.2.7.3 (Emergency Lighting), 3.2.7.4 (Emergency Power for Lighting), 3.4.5 (Exit Signs)
Canadian Electrical Code (CEC), adopted in Ontario as the OESCHow the system is wired, power sources, transfer requirementsCEC Section 46 (Emergency Power), Rule 46-400

Where Is Emergency Lighting Required? (OBC 3.2.7.3)

  • All exit corridors, stairwells, and passageways
  • Principal routes providing access to exit from open floor areas
  • All underground walkways and pedestrian tunnels
  • Rooms with occupant loads of 60 or more (assembly areas)
  • Principal routes to exits in service rooms, such as electrical rooms
  • Elevator cars (required by CSA B44, not the OBC)

Illumination Requirements

Location Average Illumination (min. 1 lux) Measurement Point
Exit corridors & stairways10 luxAt floor level
Open floor areas (principal routes)10 luxAt floor level along the route
Elevator carsPer CSA B44Elevator code (TSSA)
The 10 lux average must be maintained at the end of the battery duration period - not at full charge. Battery units dim as they discharge. Designers must account for lumen depreciation and ensure 10 lux at the 30-minute (or 1-hour or 2-hour) mark.

Battery Duration: 30 Minutes, 1 Hour, and 2 Hours

Building Type Required Duration Reason
Other buildings not listed for longer duration30 minutesMinimum duration under OBC 3.2.7.4 for many standard applications
Certain Group B and other listed buildings1 hourConfirm occupancy and building classification under OBC 3.2.7.4
High buildings in the scope of OBC 3.2.62 hoursExtended evacuation and life-safety operation time
Generator-backed emergency lightingPer OBC/NBC and CSA C282Duration, transfer, fuel supply, and testing depend on building classification and generator standard requirements

Exit Sign Requirements (OBC 3.4.5)

  • Green pictogram exit signs (running man symbol, ISO 7010) are required in new construction - red "EXIT" text signs do not comply
  • Must be visible on approach to the exit (OBC 3.4.5.1)
  • Directional arrow signs where no exit is visible
  • Must be continuously illuminated - internally, externally or photoluminescent (CAN/ULC-S572)
  • Must have integral battery backup or be on emergency power circuit

Exit signs and emergency lighting along an exit route

A typical exit corridor and stair, not a specific building. Light cones are illustrative.

Exit signs and emergency lighting along an exit routeElevation of an exit corridor with two office doors, leading to a steel door into an exit stair shown in section. A green running-man exit sign is mounted over the stair door, and a second sign with an arrow hangs from the ceiling where the exit is not yet visible. Emergency battery units with two lamp heads are mounted high on the corridor wall, their bottom at least 2 m above the floor, and another unit lights the stair. Their light reaches the floor along the egress path, marked with green arrows, at an average of 10 lux and a minimum of 1 lux.≥ 2 m10 lux avg at floor · 1 lux minEXIT STAIR123456

Detail A: exit sign types

Green pictogram signs are required in new construction

Detail A: exit sign typesLeft: a green exit sign with the white running-man pictogram and an arrow, required in new construction. Right: a red sign with the word EXIT, crossed out: it does not comply.EXITNEW CONSTRUCTIONgreen pictogramDOES NOT COMPLYred EXIT text

Parts

  1. Exit sign over the exit door: green running-man pictogram (ISO 7010), visible on approach, continuously illuminated (internally, externally or photoluminescent to CAN/ULC-S572). OBC 3.4.5

  2. Directional exit sign with an arrow where no exit is visible. OBC 3.4.5

  3. Emergency battery unit: connected to a receptacle on a normal lighting circuit in the area served; exit signs have integral batteries or an emergency power circuit. Rules 46-304, 46-400

  4. Mounting height: unit equipment with the bottom at least 2 m above the floor, wherever practicable. Rule 46-302

  5. Illumination at floor level: 10 lux average (1 lux minimum) along exit corridors, stairs and principal routes, still met at the end of the 30 min, 1 h or 2 h duration. OBC 3.2.7.3, 3.2.7.4

  6. Exit stair: emergency lighting in every exit stairwell, corridor and passageway. OBC 3.2.7.3

Testing: a monthly functional test and an annual full-duration test (30 min, 1 h or 2 h), with records kept under the Ontario Fire Code.

  • Green running-man exit sign
  • Emergency battery unit
  • Emergency light on the egress path
  • Egress path
Figure 1. Exit signs show the way; battery units keep the route lit to 10 lux at the floor for the required duration.Sources: OBC 3.2.7.3, 3.2.7.4, 3.4.5 · CEC Rules 46-302, 46-304, 46-400 · CAN/ULC-S572

Figure 1. Exit signs and emergency lighting along an exit route

CEC Section 46 - Emergency Power Supply

CEC Section 46 governs emergency power supplies, unit equipment and exit sign wiring:

CEC Rule Requirement
46-108Emergency system wiring shall be kept entirely independent of all other wiring - it may share an enclosure only in transfer switches and in exit signs and emergency lights supplied from two sources (Subrule 4)
46-202Emergency power supply types: generator conforming to CSA C282 or central battery system. Automatic transfer equipment required (Rule 46-206)
46-302Unit equipment shall be mounted with the bottom at least 2 m above floor level, wherever practicable
46-304Unit equipment supply connections - typically connected to a receptacle on a normal lighting circuit in the area served, using flexible cord and attachment plug
46-400Exit signs - must be on a dedicated connection to a power supply; location requirements set by the Ontario Building Code

Monthly & Annual Testing Requirements

Test Frequency Duration
Functional test (verify lights turn on)MonthlyNo set duration
Full duration testAnnuallyFull design duration: 30 min, 1 h or 2 h
Generator transfer testMonthly60 min at 30 % or more load (CSA C282)

Frequently Asked Questions

How long must emergency lights stay on?

OBC 3.2.7.4 sets the duration by building type and occupancy: commonly 30 minutes, 1 hour, or 2 hours. CEC Section 46 governs the electrical emergency power supply and wiring. See our fire detector guide.

Where is emergency lighting required?

Exits, public corridors, principal routes (including service rooms) and assembly areas of 60+ occupants per OBC 3.2.7.3.

What are the testing requirements?

Monthly functional test, annual full-duration test; keep records per the Ontario Fire Code.