Motor Protection Essentials: MCA, MOP & How to Size Them
Every HVAC unit, pump, and compressor on a building has a nameplate. On that nameplate, two critical values determine how you design the electrical circuit: MCA and MOP. Get them wrong, and you're either tripping breakers on startup or leaving equipment unprotected.
What is MCA (Minimum Circuit Ampacity)?
MCA stands for Minimum Circuit Ampacity. It defines the minimum current-carrying capacity that the wire and other circuit components must have. The wire you select must have an ampacity equal to or greater than the MCA value on the equipment nameplate.
How MCA is Calculated
Under the Canadian Electrical Code (CEC), Rule 28-106 sets 125% of FLC for a single motor and Rule 28-108 covers several motors; nameplate MCA follows the same logic:
MCA = 125% × FLC (Full Load Current) of the largest motor + 100% × FLC of all other motors + 100% of any heater loads
The 125% multiplier accounts for the continuous duty rating of motor circuits - motors are expected to run at full load for extended periods, and the wire must handle this thermal load safely.
Practical Example
Consider a rooftop unit (RTU) nameplate showing:
- Compressor: 28A FLC
- Supply fan motor: 8A FLC
- Electric heater: 15A
MCA = (125% × 28) + 8 + 15 = 35 + 8 + 15 = 58A
You must select a wire with ampacity ≥ 58A. Per CEC Table 2, this means #6 AWG copper (65A) in typical conditions.
The same nameplate values set the circuit for a residential heat pump's outdoor unit; the heat pump sizing guide shows where they fit in the selection.
What is MOP (Maximum Overcurrent Protection)?
MOP stands for Maximum Overcurrent Protection. It defines the maximum size of the circuit breaker or fuse protecting the circuit. You must select a breaker equal to or less than the MOP value.
How MOP is Calculated
Per CEC Rules 28-200 and 28-204 (Table 29), for motor circuits:
MOP = Maximum percentage of FLC (per CEC Table 29) for the largest motor + 100% × FLC of all other motors + 100% of heater loads
The maximum percentage depends on the protective device type and motor type:
| Protection Device | Squirrel Cage Motor | Wound Rotor Motor |
|---|---|---|
| Non-time-delay fuse | 300% | 150% |
| Time-delay fuse | 175% | 150% |
| Inverse-time circuit breaker | 250% | 150% |
| Instantaneous-trip breaker | 800% | 800% |
Continuing Our Example
Using an inverse-time circuit breaker (most common):
MOP = (250% × 28) + 8 + 15 = 70 + 8 + 15 = 93A
Round down to the next standard breaker size: 90A breaker.
Critical Rule: If the MCA requires #6 AWG wire (65A ampacity) but the MOP allows up to a 90A breaker, this is normal and correct. Motor circuits are the exception to the general rule that the breaker must not exceed wire ampacity. The motor's internal overload relay provides the running overcurrent protection.
From the nameplate to the wire and the breaker
The rooftop unit of this article’s worked example, not a specific product. Not to scale.
Detail A: unit nameplate
Fields from the worked example; no brand
Parts
Nameplate: compressor 28 A FLC, supply fan 8 A FLC, electric heater 15 A. Detail A
MCA = 125 % × 28 + 8 + 15 = 35 + 8 + 15 = 58 A. Rules 28-106, 28-108
Conductors: ampacity of at least the MCA: #6 AWG copper (65 A) in typical conditions. Table 2
MOP = 250 % × 28 + 8 + 15 = 70 + 8 + 15 = 93 A for an inverse-time breaker; rounded down to the standard size: 90 A. Rules 28-200, 28-204, Table 29
A 90 A breaker on 65 A wire is normal for a motor circuit: the breaker protects against short circuits and ground faults.
Overload relay: built into the starter (contactor + overload), set to 115–125 % of the motor FLC; it provides the running overload protection.
With a VFD, MCA and MOP are based on the VFD input current, and the VFD provides the motor overload protection.
- Branch-circuit breaker (MOP)
- Conductors in EMT (MCA)
- Liquid-tight flexible conduit
- Electric heater elements
- Gas line
Common Motor Protection Selection Table
The following table provides quick reference values for standard three-phase motors at 208V, using inverse-time circuit breakers:
| Motor HP | FLC @ 208V | MCA @ 208V | Wire Size | MOP (Breaker) |
|---|---|---|---|---|
| 5 | 16.7A | 20.9A | #10 | 45A |
| 7.5 | 24.2A | 30.3A | #8 | 70A |
| 10 | 30.8A | 38.5A | #8 | 80A |
| 15 | 46.2A | 57.8A | #6 | 120A |
| 20 | 59.4A | 74.3A | #4 | 150A |
| 25 | 74.8A | 93.5A | #3 | 200A |
| 30 | 88A | 110A | #1 | 225A |
| 40 | 114A | 142.5A | #1/0 | 300A |
| 50 | 143A | 178.8A | #3/0 | 400A |
Note: Values are approximate and based on CEC Table 44/45 FLC values for standard NEMA B design motors. Always verify with the actual equipment nameplate and local code edition.
The Role of the Overload Relay
The circuit breaker (MOP) protects against short circuits and ground faults. It does not protect the motor from overloads. That job belongs to the overload relay, which is typically:
- Built into the motor starter (contactor + overload)
- Set to 115-125% of the motor FLC
- Trips on sustained overcurrent, protecting against locked rotor and overload conditions
VFD Considerations
When a motor is fed through a Variable Frequency Drive (VFD), the circuit design changes:
- MCA/MOP are based on the VFD input current, not the motor FLC
- VFD provides electronic motor overload protection internally
- Requires VFD-rated cable on the output side to handle high-frequency switching
- Line reactor or input filter may be required to limit harmonic distortion
Reading a mechanical equipment schedule
An example schedule built from the values in this article. Read every row of every schedule against the nameplate.
| TAG | SERVICE | HP / LOAD | V / PH | MCA | MOP | STARTER / VFD | REMARKS |
|---|---|---|---|---|---|---|---|
| RTU-1 | Rooftop unit | Compressor 28 A FLC, fan 8 A, heater 15 A | Nameplate | 58 A | 90 A | Unit-mounted contactor + overload relay | #6 AWG Cu (65 A), 90 A inverse-time breaker |
| M-1 | Motor | 10 HP, FLC 30.8 A (table, 208 V) | 208 / 3 | 38.5 A | 80 A | Starter: overload set to 115–125 % of FLC | #8 AWG (selection table) |
| M-2 | Motor on a VFD | — | — | VFD input | VFD input | VFD: electronic overload protection built in | VFD-rated cable on the output side |
Quick check for each row: the same tag on the M and E drawings · conductors from the MCA · breaker no larger than the MOP · overloads in the starter or the VFD.
Electrical points
TAG: find the same tag on the mechanical schedule and on the electrical drawings; every tag needs a circuit.
HP / LOAD: the size of the load. For a simple motor, the FLC comes from CEC Table 44/45 at the system voltage (10 HP at 208 V: 30.8 A). Tables 44, 45
V / PH: the voltage and phase the values are for; the selection table in this article is for three-phase motors at 208 V.
MCA: the conductors need an ampacity of at least the MCA: RTU-1, 58 A → #6 AWG copper (65 A). Rules 28-106, 28-108 · Table 2
MOP: the breaker or fuse may not be larger than the MOP: RTU-1, 93 A calculated → a 90 A inverse-time breaker. Rules 28-200, 28-204 · Table 29
STARTER / VFD: the overload relay in the starter is set to 115–125 % of the motor FLC; with a VFD, MCA and MOP come from the VFD input current and the VFD provides the overload protection.
REMARKS: wire size and breaker; a breaker larger than the wire ampacity is normal and correct on a motor circuit.
Selection-table values are approximate (standard NEMA B motors); always verify with the actual nameplate and the local code edition.
- Column the electrical design reads
- MCA (conductors)
- MOP (largest breaker)
Frequently Asked Questions
What is MCA and MOP?
MCA = 125% of motor FLA (wire sizing). MOP = max breaker size (typically 250% FLA). See our voltage drop guide for long motor runs.
How do you size wire and breaker?
Wire: MCA (125% FLA from CEC Table 44/45). Breaker: max MOP (250% FLA inverse-time). Use conduit fill tables for raceway sizing.
Do VFDs change protection requirements?
Yes. VFDs provide built-in overload protection. Input side still needs branch circuit protection. See our VFD cable guide.