Motor Protection Essentials: MCA, MOP & How to Size Them

Rooftop unit on a curb with its fused disconnect, gas line and nameplate values MCA 58 A and MOP 90 A.

Every HVAC unit, pump, and compressor on a building has a nameplate. On that nameplate, two critical values determine how you design the electrical circuit: MCA and MOP. Get them wrong, and you're either tripping breakers on startup or leaving equipment unprotected.

What is MCA (Minimum Circuit Ampacity)?

MCA stands for Minimum Circuit Ampacity. It defines the minimum current-carrying capacity that the wire and other circuit components must have. The wire you select must have an ampacity equal to or greater than the MCA value on the equipment nameplate.

How MCA is Calculated

Under the Canadian Electrical Code (CEC), Rule 28-106 sets 125% of FLC for a single motor and Rule 28-108 covers several motors; nameplate MCA follows the same logic:

MCA = 125% × FLC (Full Load Current) of the largest motor + 100% × FLC of all other motors + 100% of any heater loads

The 125% multiplier accounts for the continuous duty rating of motor circuits - motors are expected to run at full load for extended periods, and the wire must handle this thermal load safely.

Practical Example

Consider a rooftop unit (RTU) nameplate showing:

  • Compressor: 28A FLC
  • Supply fan motor: 8A FLC
  • Electric heater: 15A

MCA = (125% × 28) + 8 + 15 = 35 + 8 + 15 = 58A

You must select a wire with ampacity ≥ 58A. Per CEC Table 2, this means #6 AWG copper (65A) in typical conditions.

The same nameplate values set the circuit for a residential heat pump's outdoor unit; the heat pump sizing guide shows where they fit in the selection.

What is MOP (Maximum Overcurrent Protection)?

MOP stands for Maximum Overcurrent Protection. It defines the maximum size of the circuit breaker or fuse protecting the circuit. You must select a breaker equal to or less than the MOP value.

How MOP is Calculated

Per CEC Rules 28-200 and 28-204 (Table 29), for motor circuits:

MOP = Maximum percentage of FLC (per CEC Table 29) for the largest motor + 100% × FLC of all other motors + 100% of heater loads

The maximum percentage depends on the protective device type and motor type:

Protection Device Squirrel Cage Motor Wound Rotor Motor
Non-time-delay fuse 300% 150%
Time-delay fuse 175% 150%
Inverse-time circuit breaker 250% 150%
Instantaneous-trip breaker 800% 800%

Continuing Our Example

Using an inverse-time circuit breaker (most common):

MOP = (250% × 28) + 8 + 15 = 70 + 8 + 15 = 93A

Round down to the next standard breaker size: 90A breaker.

Critical Rule: If the MCA requires #6 AWG wire (65A ampacity) but the MOP allows up to a 90A breaker, this is normal and correct. Motor circuits are the exception to the general rule that the breaker must not exceed wire ampacity. The motor's internal overload relay provides the running overcurrent protection.

From the nameplate to the wire and the breaker

The rooftop unit of this article’s worked example, not a specific product. Not to scale.

From the nameplate to the wire and the breakerSection through a roof. A packaged rooftop unit on a curb is cut away to show its electric heater, supply fan, starter with overload relay and compressor; its nameplate is on the left door. A fused disconnect stands beside the unit on a strut stand, connected by liquid-tight flexible conduit. Number 6 copper conductors rated 65 A run in conduit down through the roof to a panel below, where a 90 A inverse-time breaker protects the circuit. A gas line runs on roof supports.ONOFFHEATER · FAN · STARTER · COMPRESSORDISCONNECT#6 AWG CU · 65 A90 A · inverse timeMCA · CONDUCTORS125 % × 28 + 8 + 15= 58 A → #6 AWG CuMOP · INVERSE-TIME BREAKER250 % × 28 + 8 + 15 = 93 ARound down → 90 A123456

Detail A: unit nameplate

Fields from the worked example; no brand

Detail A: unit nameplateA nameplate without a brand: compressor full-load current 28 A, supply fan motor 8 A, electric heater 15 A, minimum circuit ampacity 58 A, maximum overcurrent protection 90 A.PACKAGED ROOFTOP UNITCOMPRESSOR · FLC28 ASUPPLY FAN MOTOR · FLC8 AELECTRIC HEATER15 AMIN. CIRCUIT AMPACITYMCA 58 AMAX. OVERCURRENT PROT.MOP 90 A

Parts

  1. Nameplate: compressor 28 A FLC, supply fan 8 A FLC, electric heater 15 A. Detail A

  2. MCA = 125 % × 28 + 8 + 15 = 35 + 8 + 15 = 58 A. Rules 28-106, 28-108

  3. Conductors: ampacity of at least the MCA: #6 AWG copper (65 A) in typical conditions. Table 2

  4. MOP = 250 % × 28 + 8 + 15 = 70 + 8 + 15 = 93 A for an inverse-time breaker; rounded down to the standard size: 90 A. Rules 28-200, 28-204, Table 29

  5. A 90 A breaker on 65 A wire is normal for a motor circuit: the breaker protects against short circuits and ground faults.

  6. Overload relay: built into the starter (contactor + overload), set to 115–125 % of the motor FLC; it provides the running overload protection.

With a VFD, MCA and MOP are based on the VFD input current, and the VFD provides the motor overload protection.

  • Branch-circuit breaker (MOP)
  • Conductors in EMT (MCA)
  • Liquid-tight flexible conduit
  • Electric heater elements
  • Gas line
Figure 1. MCA sizes the conductors, MOP limits the breaker: the article’s rooftop-unit example.Sources: CEC Rules 28-106, 28-108, 28-200, 28-204 · Tables 2, 29

Figure 1. From the nameplate to the wire and the breaker

Common Motor Protection Selection Table

The following table provides quick reference values for standard three-phase motors at 208V, using inverse-time circuit breakers:

Motor HP FLC @ 208V MCA @ 208V Wire Size MOP (Breaker)
516.7A20.9A#1045A
7.524.2A30.3A#870A
1030.8A38.5A#880A
1546.2A57.8A#6120A
2059.4A74.3A#4150A
2574.8A93.5A#3200A
3088A110A#1225A
40114A142.5A#1/0300A
50143A178.8A#3/0400A

Note: Values are approximate and based on CEC Table 44/45 FLC values for standard NEMA B design motors. Always verify with the actual equipment nameplate and local code edition.

The Role of the Overload Relay

The circuit breaker (MOP) protects against short circuits and ground faults. It does not protect the motor from overloads. That job belongs to the overload relay, which is typically:

  • Built into the motor starter (contactor + overload)
  • Set to 115-125% of the motor FLC
  • Trips on sustained overcurrent, protecting against locked rotor and overload conditions

VFD Considerations

When a motor is fed through a Variable Frequency Drive (VFD), the circuit design changes:

  • MCA/MOP are based on the VFD input current, not the motor FLC
  • VFD provides electronic motor overload protection internally
  • Requires VFD-rated cable on the output side to handle high-frequency switching
  • Line reactor or input filter may be required to limit harmonic distortion

Reading a mechanical equipment schedule

An example schedule built from the values in this article. Read every row of every schedule against the nameplate.

Mechanical equipment schedule: tag, service, horsepower or load, voltage and phase, MCA, MOP, starter or VFD, remarks.
TAGSERVICEHP / LOADV / PHMCAMOPSTARTER / VFDREMARKS
RTU-1Rooftop unitCompressor 28 A FLC, fan 8 A, heater 15 ANameplate58 A90 AUnit-mounted contactor + overload relay#6 AWG Cu (65 A), 90 A inverse-time breaker
M-1Motor10 HP, FLC 30.8 A (table, 208 V)208 / 338.5 A80 AStarter: overload set to 115–125 % of FLC#8 AWG (selection table)
M-2Motor on a VFD——VFD inputVFD inputVFD: electronic overload protection built inVFD-rated cable on the output side

Quick check for each row: the same tag on the M and E drawings · conductors from the MCA · breaker no larger than the MOP · overloads in the starter or the VFD.

Electrical points

  1. TAG: find the same tag on the mechanical schedule and on the electrical drawings; every tag needs a circuit.

  2. HP / LOAD: the size of the load. For a simple motor, the FLC comes from CEC Table 44/45 at the system voltage (10 HP at 208 V: 30.8 A). Tables 44, 45

  3. V / PH: the voltage and phase the values are for; the selection table in this article is for three-phase motors at 208 V.

  4. MCA: the conductors need an ampacity of at least the MCA: RTU-1, 58 A → #6 AWG copper (65 A). Rules 28-106, 28-108 · Table 2

  5. MOP: the breaker or fuse may not be larger than the MOP: RTU-1, 93 A calculated → a 90 A inverse-time breaker. Rules 28-200, 28-204 · Table 29

  6. STARTER / VFD: the overload relay in the starter is set to 115–125 % of the motor FLC; with a VFD, MCA and MOP come from the VFD input current and the VFD provides the overload protection.

  7. REMARKS: wire size and breaker; a breaker larger than the wire ampacity is normal and correct on a motor circuit.

Selection-table values are approximate (standard NEMA B motors); always verify with the actual nameplate and the local code edition.

  • Column the electrical design reads
  • MCA (conductors)
  • MOP (largest breaker)
Figure 2. The schedule columns that set the conductors, the overcurrent device and the motor protection.Sources: CEC Rules 28-106, 28-108, 28-200, 28-204 · Tables 2, 29, 44, 45

Figure 2. Reading a mechanical equipment schedule

Frequently Asked Questions

What is MCA and MOP?

MCA = 125% of motor FLA (wire sizing). MOP = max breaker size (typically 250% FLA). See our voltage drop guide for long motor runs.

How do you size wire and breaker?

Wire: MCA (125% FLA from CEC Table 44/45). Breaker: max MOP (250% FLA inverse-time). Use conduit fill tables for raceway sizing.

Do VFDs change protection requirements?

Yes. VFDs provide built-in overload protection. Input side still needs branch circuit protection. See our VFD cable guide.

Related service

Electrical engineering

ETEM can assess system conditions, connected equipment and protection requirements to define the appropriate study, coordination or mitigation scope.

Electrical engineering